This paper presents HFC32 average boiling heat transfer coefficients and pressure drops measured inside a small Brazed Plate Heat Exchanger (BPHE): the effects of heat flux, saturation temperature (pressure), and outlet conditions are investigated. The experimental tests were carried out at four different saturation temperatures (5, 10, 15, and 20 degrees C) and four different evaporator outlet conditions (vapour quality around 0.80 and 1.00, vapour super-heating around 5 and 10 degrees C). The average heat transfer coefficients show great sensitivity to heat flux and outlet conditions and weak sensitivity to saturation temperature (pressure). The saturated boiling heat transfer coefficients were compared with a new model for refrigerant vaporisation inside BPHE (Longo et al., 2015): the mean absolute percentage deviation between calculated and experimental data is 4.7%. The heat transfer and pressure drop measurements are complemented with a IR thermography analysis for a better understanding of the vaporisation process inside a BPHE.
HFC32 vaporisation inside a Brazed Plate Heat Exchanger (BPHE): Experimental measurements and IR thermography analysis
LONGO, GIOVANNI ANTONIO;MANCIN, SIMONE;RIGHETTI, GIULIA;ZILIO, CLAUDIO
2015
Abstract
This paper presents HFC32 average boiling heat transfer coefficients and pressure drops measured inside a small Brazed Plate Heat Exchanger (BPHE): the effects of heat flux, saturation temperature (pressure), and outlet conditions are investigated. The experimental tests were carried out at four different saturation temperatures (5, 10, 15, and 20 degrees C) and four different evaporator outlet conditions (vapour quality around 0.80 and 1.00, vapour super-heating around 5 and 10 degrees C). The average heat transfer coefficients show great sensitivity to heat flux and outlet conditions and weak sensitivity to saturation temperature (pressure). The saturated boiling heat transfer coefficients were compared with a new model for refrigerant vaporisation inside BPHE (Longo et al., 2015): the mean absolute percentage deviation between calculated and experimental data is 4.7%. The heat transfer and pressure drop measurements are complemented with a IR thermography analysis for a better understanding of the vaporisation process inside a BPHE.Pubblicazioni consigliate
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.